GOST 13109 97 electrical energy. Terms and Definitions


page 1



page 2



page 3



page 4



page 5



page 6



page 7



page 8



page 9



page 10



page 11



page 12



page 13



page 14



page 15



page 16



page 17



page 18



page 19



page 20



page 21



page 22



page 23

ELECTRIC ENERGY

REQUIREMENTS FOR THE QUALITY OF ELECTRIC ENERGY IN GENERAL PURPOSE ELECTRICAL NETWORKS

Price 5 kopecks.


Official publication

USSR STATE COMMITTEE ON STANDARDS Moscow

UDC 621.311:621.332: 006.354 Group E02

STATE STANDARD OF THE USSR UNION

ELECTRIC ENERGY

Requirements for the quality of electrical energy in general purpose electrical networks GOST

Electrical energy. Requirements for quality of 13109_87

electrical energy in general-purpose electrical networks

Date of introduction 01/01/89 Failure to comply with the standard is punishable by law

The standard establishes requirements for the quality of electrical energy in general-purpose electrical networks of alternating three-phase and single-phase current with a frequency of 50 Hz at the points to which receivers or consumers of electrical energy are connected.

The standard does not establish requirements for the quality of electrical energy in electrical networks: special purpose (for example, contact traction, communications); mobile installations (eg trains, aircraft, ships); autonomous power supply systems; temporary appointment; connected to mobile power sources.

The terms used in the standard and their explanations are given in Appendix 1.

1. NOMENCLATURE OF ELECTRIC ENERGY QUALITY INDICATORS

1.1. Electric energy quality indicators (EPQ) are divided into two groups: main PQI and additional PQI.

Official publication

The main PKE determine the properties of electrical energy that characterize its quality. Additional PKE are forms of recording the main PKE used in other regulatory and technical documents.

Reproduction is prohibited © Standards Publishing House, 1988

Note. The voltage change ranges normalized by this standard include single voltage changes of any shape with a repetition rate of more than two times per minute (1/60 Hz) and swings with a repetition frequency from two times per minute to one per hour, with an average voltage change rate of more than 0.1%/s for incandescent lamps and 0.2%/s for other electrical consumers.

1.3. The dose of voltage fluctuations (f) in percent squared is calculated using the formula

where gf is the coefficient for reducing the actual ranges of voltage changes to equivalent ones, determined in accordance with table. 2;

@ - averaging time interval equal to 10 minutes;

S(f,t)-frequency spectrum of the voltage change process at time t.

For periodic or close to periodic voltage changes, it is possible to calculate the dose of voltage fluctuations (φ) using the formula

Г VgfhUj* dt, (6)

0 f±0

where 6Uf are the effective values ​​of the components of the Fourier series expansion of voltage changes with a swing of 6U t, in accordance with clause 1.2 of Appendix 2).

Table 3

Frequency of voltage changes,

Coefficient

Frequency of voltage changes,

Coefficient

1.4. The coefficient of non-sinusoidality of the voltage curve (Kaeu) in percentage is calculated using the formula

*HCt/=100 V 21 ^(2 R)/^nom, (7)

where U(n) is the effective value of the lth harmonic component of voltage, V, kV;

n-order of the harmonic component of voltage;

N is the order of the last of the harmonic voltage components taken into account.

1) do not take into account harmonic components of the order of n>40 and (or) whose values ​​are less than 0.3%;

2) calculate this PKE using the formula

* Н с.с/=1°0 У £ ’Uf a) IU ( (8)
g P=2

where (7(1) is the effective value of the fundamental frequency voltage V, kV.

Note. The relative error in determining Kasi using formula (8) compared to formula (7) is numerically equal to the voltage deviation 1/(1) FROM Unom.

1.5. The coefficient of the lth harmonic component of the voltage Kii) in* percent is calculated using the formula

where U(n) is the effective value of the nth harmonic component of voltage V, kV.

It is allowed to calculate this PKE using the formula

/C i(i g=100

where U(i) is the effective value of the fundamental frequency voltage V, kV.

Note. The relative error of determination using formula (10) compared to formula (9) is numerically equal to the voltage deviation

0(\) FROM Unom*

1.6. The negative sequence voltage coefficient (K 2 u) in percent is calculated using the formula

^2(1)/^nom" 00

where U 2 (d is the effective value of the negative sequence voltage of the fundamental frequency of the three-phase voltage system, V, kV;

Ubovl - rated value of phase-to-phase voltage, V, kV.

The effective value of the negative sequence voltage of the fundamental frequency (£/ 2 p>) is calculated by the formula



SVP) ^AS(1)










where C/vap), Vvsp ^assh are the effective values ​​of the phase-to-phase voltages of the fundamental frequency. V, kV.

When determining this PQ it is allowed:

1) calculate U2(о using the approximate formula

^2(1)”®"® [^НБ (1)1* О 3)

where £/ nb w, Un mp) are the largest and smallest effective values ​​of the three phase-to-phase voltages of the fundamental frequency, V, kV.

Note. The relative error in determining Kj using formula (13) instead of formula (12) does not exceed ±8%;

2) use when calculating U20) instead of the effective values ​​of phase-to-phase voltages of the fundamental frequency, the effective values ​​of phase-to-phase voltages determined taking into account all harmonic components, if the non-sinusoidal coefficient of the voltage curve (in accordance with the requirements of clause 1.4 of Appendix 2) does not exceed 5%;


Kgs;-SO ^2(1)/^1(1) O 4)


where Uko is the effective value of the positive sequence voltage of the fundamental frequency. V, kV.

Note. The relative error in determining Kiu using formula (14) compared to formula (11) is numerically equal to the deviation of voltage Uni) from and in ohms.

1.7. The zero sequence voltage coefficient Ko and a three-phase four-wire system in percent is calculated using the formula

K oi =100 and Shch1) /and a0M "f, (15)

where £/o(n-rms value of the zero sequence of the fundamental frequency B, kV;

Ud, ohm-f - rated value of phase voltage V, kV.



where Uyour, ^sv(1), ^Asp) are the effective values ​​of phase-to-phase voltages of the fundamental frequency, V, kV;

C/a(i>, C/b(i>) are the effective values ​​of phase voltages of the fundamental frequency, V, kV.

When determining this PQ it is allowed:

1) calculate (Jon) using an approximate formula

£/0(^=0.62 [^nv.f(1) ^nm.f(1)1* O 7)

where £/ nb. f(1) (^nm.f(1)” greatest and smallest effective values

of three phase voltages of fundamental frequency, V, kV.

and A u^aMUcs-U,)! V 3

Uв np=£VH^c-^i)/ VI «с Шг^с+^ва-)/V 3

If there is a negative sequence voltage in the phase-to-phase voltages, the values ​​of C/NB# f(1) and Tssh.fsh are determined as the largest and smallest values ​​of the given phase voltages (with the negative sequence voltage excluded). The given phase voltages are determined by the formula

Note. The relative error in determining Koi using formula (17) instead of formula (16) does not exceed ±10%;

2) use instead of the effective values ​​of phase-to-phase and phase-to-phase voltages of the fundamental frequency the effective values ​​of voltages determined taking into account all harmonic components, if the coefficient of non-sinusoidality of the voltage curves does not exceed 5%;

3) calculate this PKE using the formula

100 V 3 SG 0 (1)1(/C)), (19)

where L/id) is the effective value of the positive sequence voltage of the fundamental frequency. V, kV.

Note. The relative error in determining Koi using formula (19) compared to formula (15) is numerically equal to the value of the deviation of voltage £/cp from U nom.

1.8. Frequency deviation (Δf) in hertz is calculated using the formula

A /==/-/nom"



where / is the frequency value, Hz;

/nom - nominal frequency value, Hz.

1.9. The duration of the voltage dip (A/p) in seconds (Fig. 3) is calculated using the formula


where /n, /k are the initial and final moments of the voltage dip, s.

1.10. Pulse voltage in relative units (fit/*imi) in accordance with the drawing. 4 is calculated by the formula

a£L»imp = Dimp ~. (22)


where Uimp is the value of the pulse voltage. V, kV.

2. Additional PKE

2.1. The amplitude modulation coefficient (/(mod) in percent in accordance with Fig. 5 is calculated using the formula



^НБ.а~^НМ.а



where Unv.a, t/nm.a are the largest and smallest amplitudes of the modulated voltage. V, kV.

With periodic voltage modulation, the relationship between the peak-to-peak voltage change (fit/*) and the amplitude modulation coefficient is determined by the formula

bU t =2 /(mod- (24)


2.2. The unbalance coefficient of phase-to-phase voltages (/(sky) in percent is calculated using the formula







where U H b* U nm is the largest and smallest effective value of the three phase-to-phase voltages. V, kV.

When the voltage non-sinusoidal coefficient Kis and (determined in accordance with the requirements of clause 1.4 of Appendix 2), not exceeding 5%, the ratio between the negative sequence coefficient (Ki) and the unbalance coefficient of phase-to-phase voltages K k e b, is determined by the approximate formula


K 2i = 0.62 / C„ eb. (26)

Note: The relative error in calculating Kiu using formula (26) does not exceed ±8%.

2.3. The phase voltage unbalance coefficient (Kneb.f) as a percentage is calculated using the formula


^НВ, f~~^НМ. f ^nom. f



where Unm.f are the largest and smallest effective values ​​from

three phase voltages. V, kV;

^nom.ph - rated value of phase voltage. V, kV.

When the voltage non-sinusoidal coefficient Kis and (determined in accordance with the requirements of clause 1.4 of Appendix 2) does not exceed the 5% ratio between the zero-sequence voltage coefficient (/(oo) and the phase voltage unbalance coefficient /Snev.F, determined by approximate formula

Koir=0.62 K iev. f. (28)

Note. The relative error of calculating Koi according to formula (28) does not exceed ±8%.

3. Auxiliary parameters of electrical energy

3.1. The frequency of voltage changes (F), s -1, min-1, h~ 1, is calculated using the formula

where /u is the number of voltage changes during time T;

T - measurement time interval, s, min, h.

3.2. Time interval between voltage changes (At it t+1) in accordance with fig. 2, s, min, h, calculated by the formula

where t i+ 1, fi are the initial moments of successive voltage changes, s, min, h, in accordance with the diagram. 2.

If the time interval between the end of one change and the beginning of the next, occurring in the same direction, is less than 30 ms, then these changes are considered as one in accordance with the line. 2.

3.3. The depth of the voltage dip (bU a) in percent in accordance with the drawing. 3 is calculated by the formula

6th g p== .Unou7-Utt, 100| (31)

where Umin is the minimum effective voltage value during a voltage dip. V, kV.

TP (YG p, M p) M





3.4. The intensity of voltage dips (t#) as a percentage is calculated using the formula

where t(bS/n, D*n) is the number of dips of depth 6 £/t and duration for the considered time interval Г;

M is the total number of voltage dips during the considered time interval T.

3.5. The duration of the voltage pulse at the level of 0.5 of its amplitude (D*imp o.b) in microseconds, milliseconds in accordance with the drawing. 5 is calculated by the formula

d ^imp o.5“^ to 1

where t Hi t K are the moments of time corresponding to the intersection of the voltage pulse curve with a horizontal line drawn at half the pulse amplitude, μs, ms.

APPENDIX 9 Mandatory

METHOD FOR DETERMINING THE ACCEPTANCE OF VOLTAGE FLUCTUATIONS FOR LIGHTING INSTALLATIONS

The condition for the admissibility of a set of voltage change ranges, each of which does not exceed the values ​​determined in accordance with the lines. 1, is

where D* d* is the minimum permissible time interval between swings with an amplitude of 6Ut, determined by the lower scale of lines. 1;

T is the total time of observation of the swings.

Example. In 10 minutes, 12 peak-to-peak amplitudes of 4.8% (first group of peaks), 30 peak-to-peak amplitudes of 1.7% (second group), and 100 peak-to-peak amplitudes of 0.9% (third group) were recorded in the network. Determine the admissibility of power supply from this network of fluorescent lamps.

1. Along the curve 3 lines. 1 we determine: for 6С/l ~ 4.8% Dg d1 = 30 s, for 6С/ #2 = “1.7% D*d2 = 1 s, for bShz -0.9% A/dz-0.1 With.

2. By determining by (34) the minimum time for which a given number of swings with the specified amplitude is permissible:

12*30+30-1+100-0.1 =400 s<600 с.

Conclusion. Power supply from this point of the fluorescent lamp network is acceptable.


Permissible voltage ranges


F - frequency of voltage changes; M d - time interval between swings


Voltage fluctuations


6С/^П - range of periodic oscillations (7 ranges of voltage changes during time T p fit/81/^5 - range of non-periodic oscillations


Voltage dip



Periodic amplitude modulation



1.2. The main PKEs include: voltage deviation U, voltage change range bUt, voltage fluctuation dose f, voltage curve non-sinusoidal coefficient /Cves/, coefficient of the nth harmonic component UiY), negative sequence voltage coefficient /Csi, zero sequence voltage coefficient Koi, frequency deviation Df, voltage dip duration Dt n, pulse voltage 100;
δ U (+) = [(U m(+) – U 0) / U 0 ] 100,

Where U m(–) , U m(+) – power supply voltage values, less than U 0 and larger U 0 respectively, averaged over a time interval of 10 minutes in accordance with the requirements of GOST R 51317.4.30, subsection 5.12;
U 0 – voltage equal to standard rated voltage U nom or matched voltage U With.

For the above CE indicators, the following standards are established: positive and negative voltage deviations at the point of electricity transmission should not exceed 10% of the nominal or agreed voltage value for 100% of the time of the one week interval.

In GOST 13109-97, the steady-state voltage deviation is calculated taking into account only the 1st voltage harmonic U (1) :

δ U= (U (1) – U nom) / U nom

and is characterized by normally permissible and maximum permissible values ​​at the terminals of electrical receivers equal to ±5 and ±10%, respectively.

The standards (numerical values) for permissible frequency deviations in synchronized power supply systems are the same as in GOST 13109-97: ±0.2 Hz for 95% of the time of an interval of one week and ±0.4 Hz for 100% of the time of the interval in one week.

The limits for permissible frequency deviations in isolated power supply systems with stand-alone generator sets not connected to synchronized electrical power transmission systems are less stringent: ±1 Hz for 95% of the time of a one-week interval and ±5 Hz for 100% of the time of a one-week interval week.

FE indicators related to the harmonic components of voltage are:

  • values ​​of the coefficients of harmonic voltage components up to the 40th order TO U(n) as a percentage of the fundamental harmonic component voltage U 1 at the power transmission point;
  • the value of the total coefficient of harmonic components of the voltage (the ratio of the root mean square value of the sum of all harmonic components up to the 40th order to the root mean square value of the fundamental component) K U,% at the point of electricity transmission.

The norms (numerical values) of FE indicators related to non-sinusoidality and voltage asymmetry in this standard are kept unchanged as in GOST 13109-97, but CE indicators related to voltage non-sinusoidality are measured and assessed taking into account the influence of not only higher harmonics, but also groups of closely spaced combinational (interharmonic) components in accordance with GOST R 51317.4.7-2008, subsections 3.2, 3.3.

Taking into account the requirements of GOST R 51317.4.30-2008 for classes and measuring instruments of CE indicators, this standard establishes standards for CE indicators in the form of values ​​measured over a single time interval of class A measurements, equal to 10 periods of network voltage 50 Hz (0.2 s) s averaging at each time interval of 10 minutes over a week.

According to the requirements of GOST 13109-97, FE indicators must be measured over the main time interval from 0.1 to 0.5 s with averaging over a time interval of 3 s or 1 min (for voltage deviations) during every 24 hours of the weekly cycle.

Thus, the estimated time interval for measuring CE indicators to assess their compliance with the requirements of the new standard is 1 week, and not 24 hours, as required by GOST 13109-97.

RUSSIAN AND EUROPEAN STANDARDS

The main differences between GOST R 54149-2010 and the European standard EN 50160: 2010 are the requirements for a number of PKE: EN 50160 does not have maximum permissible values ​​for some of the KE indicators; an important indicator for our networks is the zero-sequence voltage asymmetry coefficient; less stringent requirements have been introduced. in comparison with GOST R 54149-2010, requirements for frequency and voltage deviations are unreasonable for Russian networks, incomplete data for CE indicators in high-voltage networks, etc.

The requirements of the European standard are designed for use in electrical networks of countries that have different requirements for the design of electrical networks and a different level of condition of these networks compared to the Russian one.

When revising GOST 13109-87 and developing the edition of GOST 13109-1997, CE indicators and standards were analyzed and discussed in detail and were reasonably accepted. In the period since the entry into force of GOST 13109-1997 (1999), the technical state of our networks does not yet provide grounds for revising CE standards in the direction of their mitigation and harmonization with European ones.

As for the structure and content of the standard, general approaches to CE standardization and requirements for methods for measuring CE indicators, the provisions of the new domestic and European standards are quite close.

The approved GOST R 54149-2010 is included in the national standardization program of the Russian Federation for its re-registration into the interstate standard of the EurAsEC organization.

LITERATURE

  1. IEC 61000-4-30: 2008 Electromagnetic compatibility (EMC) – Part 4-30: Testing and measurement techniques – Power quality measurement methods.
  2. IEC 61000-4-7: 2002 Electromagnetic compatibility (EMC) – Part 4-7: Testing and measurement techniques – General guide on harmonics and interharmonics measurement and instrumentation, for power supply systems and equipment connected thereto.
  3. GOST R 51317.4.30–2008 (IEC 61000-4-30:2008). Electromagnetic compatibility of technical equipment. Methods for measuring electrical energy quality indicators.
  4. GOST R 51317.4.7–2008 (IEC 61000-4-30:2008). Electromagnetic compatibility of technical equipment. General guidance on measuring instruments and measurements of harmonics and interharmonics for power supply systems and technical equipment connected to them.
  5. EN 50160:2010 Voltage characteristics of electricity supplied by public electricity networks.
  6. GOST 29322-92. Standard voltages.

General provisions

GOST establishes 11 main indicators of power quality (PQE):

1) frequency deviation;

2) steady-state voltage deviation;

3) voltage change range;

4) dose of flicker (flicker or fluctuation);

5) distortion factor of the sinusoidal voltage curve;

b) coefficient of the nth harmonic component of voltage

7) negative sequence voltage asymmetry coefficient;

8) zero-sequence voltage asymmetry coefficient;

9) duration of voltage dip;

10) pulse voltage

11) temporary overvoltage coefficient. In table 2.24. The properties of electrical energy, their characterizing indicators and the most likely culprits for the deterioration of CE are given.

Table 2.24. Properties of electrical energy, indicators and most

probable culprits for deterioration of CE

Properties of electrical energy

CE indicator

Most Likely Culprits

deterioration of CE

Voltage deviation

Steady Deviation

voltage

Energy supply organization

Voltage fluctuations

Voltage range Flicker dose

Consumer with variable load

Non-sinusoidal voltage

Voltage curve sinusoidal distortion coefficient Coefficient

nth harmonic voltage component

Consumer with nonlinear load

Unbalance of three-phase voltage system

Negative sequence voltage asymmetry coefficient, Zero sequence voltage asymmetry coefficient

Consumer with asymmetric load

Frequency deviation

Frequency deviation

Energy supply organization

Voltage dip

Voltage dip duration

Energy supply organization

Voltage pulse

Pulse voltage

Energy supply organization

Temporary overvoltage

Temporary overvoltage factor

Energy supply organization

Normally permissible and maximum permissible values ​​at the point of common connection to electrical networks with different rated voltages are given in table. 2.25.

Table 2.25 . GOST requirements for limiting the sinusoidal distortion coefficient (KU)

Normally permissible values ​​of the coefficient of the nth harmonic component of voltage are given in table. 2.26.

In table 2.27. summary data on PKE standards is provided.


Table 2. 26 Normally acceptable coefficient valuesnth harmonic voltage component

Harmonic number, non-multiple 3, odd at, kV

Harmonic number multiple of 3*, odd at, kV

Even harmonic number at, kV

Harmonic no.

Harmonic no.

Harmonic no.

*Normally permissible values ​​given for n equal to 3 and 9 refer to single-phase electrical networks. In three-phase three-wire electrical networks, these values ​​are taken to be half those given in the table.

Table 2. 27 Electrical energy quality standards

FE indicator, units. measurements

normally acceptable

maximum permissible

Steady-state voltage deviation, %

Voltage change range, %

Flicker dose, rel. units:

short-term

long-term

Voltage curve sinusoidal distortion coefficient, %

Coefficient of the nth harmonic component of voltage, %

Negative sequence voltage asymmetry coefficient, %

Zero sequence voltage asymmetry factor, %

Frequency deviation, Hz

Voltage dip duration, s

Pulse voltage, kV

Temporary overvoltage factor, rel. units

According to table 2. 25

According to table 2. 26

According to table 2. 25

According to table 2. 26